Features & Specifications
Features
ADVANCED CAPABILITIES
-
Sensor Inputs: Connect up to six external sensors to monitor a variety of equipment and conditions. Each input zone can be connected to a temperature sensor, an analog
transducer, or a dry contact switch.
-
Web Status: Live status and history is only a webpage away. The Web600 built in web
server provides quick and easy information about your monitored conditions. Even
time stamped history reports are readily available online.
-
Alarm Notification: When monitored conditions exceed normal values, the Web600 will
notify you immediately by sending out e-mail alarm messages, and even text messages.
Up to eight people can be contacted to make sure that proper action is taken.
-
Web Programming: Built in web server for easy access to programming and status.
Just point your browser to the Web600’s webpage and fill in the blanks for a quick configuration.
-
Optional battery backup: With the addition of the optional battery backup module,
the Web600 can monitor for power failures and stay operational for two full hours
while the power is out.
-
- Alarm Notification Methods:
- E-Mail, Text Messages, SNMP Traps
-
- 8 Alarm escalation levels
-
- Comprehensive scheduling per input, profile, and alarm destination
-
- Destinations:
- 8 Programmable User Profiles
-
- 4 programmable alarm destinations per profile
-
- Communication Types:
- E-Mail – SMTP
-
- Text Messages
-
- Web page – Supported formats HTTP, PDA, WAP, and XML
-
- SNMP – MIB with Traps, GET, GETNEXT, and SET
-
- MODBUS®/TCP Slave Conformance Class 0 and 1
-
- Inputs:
- 6 Universal Inputs
-
- Normally Closed / Normally Open Dry Contact
-
- 2.8K / 10K Thermistor
-
- 4-20mA Current Loop
-
- 12 Bit Resolution
-
- Data Logging:
- 32,000 Samples (all samples include data date and time)
-
- 1 second to 1 month sampling rate
-
- User programmable channel selection (Zones 1-6, Battery, and Input Power)
-
- Communication Ports:
- Ethernet 10/100Base–T
-
- Local indicators:
- Alarm Status LED
-
- Power Status LED
-
- Ethernet link and Activity LEDs
-
- Power Requirements
- External transformer 120VAC 60Hz
-
- Optional Battery Backup - Module (FGD-W610)
-
- Provides 2 hours of backup
-
- Operating conditions:
- 0-90% RH, non–condensing
-
- 0-50°C (32–122°F)
-
- Physical properties:
- 5.5" x 3.25" x 1.25"
-
- 0.5lbs
-
- Standards:
- FCC Part 15–B Compliant